Login

Subtype

ECL-PAC-04

Certificate Holder
ECL Nexus
13, Boulevard Pereire
75017 Paris
France
Registration number
ICIM-PDC-000141
Certification Body
ICIM S.p.A.
Subtype title
ECL-PAC-04
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,500 kg

Certification Date
20.05.2022
Testing basis
V9
Phase-out Date
30.10.2025
Generate PDF Export model CSV
  • Number of models 1

Models

ECLPAC04X.ST / ECLPAC04X.KA Phasing out on 30.10.2025
Configure model
Model name
ECLPAC04X.ST / ECLPAC04X.KA
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
1x230V 50Hz
Phase-out Date
30.10.2025

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.76 kW

4.53 kW

El input

1.00 kW

1.54 kW

COP

4.76

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

1.37 kW

Cooling capacity

4.33

EER

3.16

EN 14825

+7°C/+12°C

Pdesignc

4.33 kW

SEER

4.28

Pdc Tj = 35°C

4.33 kW

EER Tj = 35°C

3.16

Pdc Tj = 30°C

3.16 kW

EER Tj = 30°C

3.85

Cdc Tj = 30 °C

1.000

Pdc Tj = 25°C

2.67 kW

EER Tj = 25°C

4.85

Cdc Tj = 25 °C

1.000

Pdc Tj = 20°C

2.98 kW

EER Tj = 20°C

6.34

Cdc Tj = 20 °C

1.000

Poff

19 W

PTO

0 W

PSB

19 W

PCK

30 W

Annual energy consumption Qce

606 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

57 dB(A)

57 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

135 %

Prated

4.00 kW

4.00 kW

SCOP

4.56

3.45

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-15 °C

Pdh Tj = -7°C

3.90 kW

3.90 kW

COP Tj = -7°C

3.01

2.26

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

2.40 kW

2.40 kW

COP Tj = +2°C

4.53

3.32

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

2.80 kW

2.80 kW

COP Tj = +7°C

5.57

4.35

Cdh Tj = +7 °C

0.969

0.976

Pdh Tj = 12°C

3.30 kW

3.30 kW

COP Tj = 12°C

7.01

6.01

Cdh Tj = +12 °C

0.963

0.969

Pdh Tj = Tbiv

3.90 kW

3.90 kW

COP Tj = Tbiv

3.01

2.26

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.80 kW

3.90 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.77

2.06

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

60 °C

60 °C

Poff

19 W

19 W

PTO

22 W

22 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.20 kW

0.10 kW

Annual energy consumption Qhe

1988 kWh

2624 kWh