Login

Subtype

Sheen EVO/EVO 2.0 - 30.2, 35.2, 40.2

Certificate Holder
Clivet s.p.a.
Via camp lonc 25 c.ap.
I-32032 z.i. Villapaiera - Feltre (BL)
Italy
Registration number
ICIM-PDC-000132 / 01
Certification Body
ICIM S.p.A.
Subtype title
Sheen EVO/EVO 2.0 - 30.2, 35.2, 40.2
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

17,500 kg

Certification Date
21.02.2022
Testing basis
HP KEYMARK certification scheme rules rev. no. 9
Generate PDF Export model CSV Download certificate
  • Number of models 13

Models

WSAN-YSi 30.2
Configure model
Model name
WSAN-YSi 30.2
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

77.50 kW

El input

18.67 kW

COP

4.15

Cooling

EN 14511-2

El input

22.23 kW

Cooling capacity

68.90

EER

3.09

EN 14825

Pdesignc

68.90 kW

SEER

4.14

Pdc Tj = 35°C

68.90 kW

EER Tj = 35°C

3.09

Pdc Tj = 30°C

49.07 kW

EER Tj = 30°C

3.88

Cdc Tj = 30 °C

0.900

Pdc Tj = 25°C

31.48 kW

EER Tj = 25°C

4.63

Cdc Tj = 25 °C

0.900

Pdc Tj = 20°C

23.76 kW

EER Tj = 20°C

5.05

Cdc Tj = 20 °C

0.900

Poff

104 W

PTO

244 W

PSB

104 W

PCK

0 W

Annual energy consumption Qce

9916 kWh

Average Climate

EN 12102-1

Sound power level outdoor

82 dB(A)

EN 14825

ηs

160 %

Prated

51.00 kW

SCOP

4.06

Tbiv

-7 °C

TOL

-15 °C

Pdh Tj = -7°C

45.02 kW

COP Tj = -7°C

2.75

Cdh Tj = -7 °C

0.900

Pdh Tj = +2°C

28.17 kW

COP Tj = +2°C

4.18

Cdh Tj = +2 °C

0.900

Pdh Tj = +7°C

26.16 kW

COP Tj = +7°C

5.00

Cdh Tj = +7 °C

0.900

Pdh Tj = 12°C

31.74 kW

COP Tj = 12°C

6.88

Cdh Tj = +12 °C

0.900

Pdh Tj = Tbiv

45.02 kW

COP Tj = Tbiv

2.75

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

42.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.14

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

WTOL

54 °C

Poff

104 W

PTO

508 W

PSB

104 W

PCK

0 W

Supplementary Heater: Type of energy input

n/a

Supplementary Heater: PSUP

8.20 kW

Annual energy consumption Qhe

25834 kWh

WSAN-YSi 35.2
Configure model
Model name
WSAN-YSi 35.2
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

86.00 kW

El input

21.45 kW

COP

4.01

Cooling

EN 14511-2

El input

28.40 kW

Cooling capacity

79.80

EER

2.81

EN 14825

Pdesignc

79.80 kW

SEER

4.04

Pdc Tj = 35°C

79.80 kW

EER Tj = 35°C

2.81

Pdc Tj = 30°C

58.80 kW

EER Tj = 30°C

3.65

Cdc Tj = 30 °C

0.900

Pdc Tj = 25°C

37.80 kW

EER Tj = 25°C

4.48

Cdc Tj = 25 °C

0.900

Pdc Tj = 20°C

24.28 kW

EER Tj = 20°C

5.08

Cdc Tj = 20 °C

0.900

Poff

104 W

PTO

293 W

PSB

104 W

PCK

0 W

Annual energy consumption Qce

11841 kWh

Average Climate

EN 12102-1

Sound power level outdoor

83 dB(A)

EN 14825

ηs

159 %

Prated

55.00 kW

SCOP

4.06

Tbiv

-7 °C

TOL

-15 °C

Pdh Tj = -7°C

48.43 kW

COP Tj = -7°C

2.68

Cdh Tj = -7 °C

0.900

Pdh Tj = +2°C

29.76 kW

COP Tj = +2°C

4.16

Cdh Tj = +2 °C

0.900

Pdh Tj = +7°C

26.16 kW

COP Tj = +7°C

5.00

Cdh Tj = +7 °C

0.900

Pdh Tj = 12°C

31.82 kW

COP Tj = 12°C

6.84

Cdh Tj = +12 °C

0.900

Pdh Tj = Tbiv

48.30 kW

COP Tj = Tbiv

2.68

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

47.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.09

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

WTOL

54 °C

Poff

104 W

PTO

540 W

PSB

104 W

PCK

0 W

Supplementary Heater: Type of energy input

n/a

Supplementary Heater: PSUP

7.80 kW

Annual energy consumption Qhe

27859 kWh

WSAN-YSi 40.2
Configure model
Model name
WSAN-YSi 40.2
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

96.10 kW

El input

25.63 kW

COP

3.75

Cooling

EN 14511-2

El input

37.72 kW

Cooling capacity

97.30

EER

2.65

EN 14825

Pdesignc

88.40 kW

SEER

3.94

Pdc Tj = 35°C

88.40 kW

EER Tj = 35°C

2.65

Pdc Tj = 30°C

65.10 kW

EER Tj = 30°C

3.55

Cdc Tj = 30 °C

0.900

Pdc Tj = 25°C

42.80 kW

EER Tj = 25°C

4.46

Cdc Tj = 25 °C

0.900

Pdc Tj = 20°C

23.30 kW

EER Tj = 20°C

4.79

Cdc Tj = 20 °C

0.900

Poff

104 W

PTO

414 W

PSB

104 W

PCK

0 W

Annual energy consumption Qce

13478 kWh

Average Climate

EN 12102-1

Sound power level outdoor

83 dB(A)

EN 14825

ηs

159 %

Prated

56.00 kW

SCOP

4.04

Tbiv

-7 °C

TOL

-15 °C

Pdh Tj = -7°C

49.34 kW

COP Tj = -7°C

2.67

Cdh Tj = -7 °C

0.900

Pdh Tj = +2°C

31.85 kW

COP Tj = +2°C

4.24

Cdh Tj = +2 °C

0.900

Pdh Tj = +7°C

26.15 kW

COP Tj = +7°C

4.73

Cdh Tj = +7 °C

0.900

Pdh Tj = 12°C

32.51 kW

COP Tj = 12°C

6.78

Cdh Tj = +12 °C

0.900

Pdh Tj = Tbiv

49.34 kW

COP Tj = Tbiv

2.67

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

53.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.00

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

WTOL

54 °C

Poff

104 W

PTO

690 W

PSB

104 W

PCK

0 W

Supplementary Heater: Type of energy input

n/a

Supplementary Heater: PSUP

3.00 kW

Annual energy consumption Qhe

28523 kWh

WiSAN-YSE1 EXC-SC 30.2
Configure model
Model name
WiSAN-YSE1 EXC-SC 30.2
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

78.60 kW

75.70 kW

El input

18.20 kW

29.80 kW

COP

4.31

2.54

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

78 dB(A)

78 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

170 %

125 %

Prated

53.40 kW

58.02 kW

SCOP

4.33

3.20

Tbiv

-7 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

47.21 kW

47.66 kW

COP Tj = -7°C

2.73

1.96

Cdh Tj = -7 °C

0.970

0.970

Pdh Tj = +2°C

30.76 kW

29.59 kW

COP Tj = +2°C

4.34

3.12

Cdh Tj = +2 °C

0.970

0.970

Pdh Tj = +7°C

35.04 kW

39.10 kW

COP Tj = +7°C

5.60

4.42

Cdh Tj = +7 °C

0.970

0.970

Pdh Tj = 12°C

40.87 kW

33.21 kW

COP Tj = 12°C

7.28

6.07

Cdh Tj = +12 °C

0.970

0.970

Pdh Tj = Tbiv

47.21 kW

49.09 kW

COP Tj = Tbiv

2.73

2.02

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

44.78 kW

45.04 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.42

1.59

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.970

0.970

WTOL

35 °C

55 °C

Poff

110 W

110 W

PTO

200 W

200 W

PSB

110 W

110 W

PCK

10 W

10 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

8.59 kW

12.98 kW

Annual energy consumption Qhe

25443 kWh

37519 kWh

WiSAN-YSE1 EXC-SC 35.2
Configure model
Model name
WiSAN-YSE1 EXC-SC 35.2
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

87.50 kW

86.10 kW

El input

22.10 kW

35.20 kW

COP

3.95

2.44

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

81 dB(A)

81 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

169 %

125 %

Prated

58.90 kW

62.63 kW

SCOP

4.29

3.19

Tbiv

-7 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

52.10 kW

51.45 kW

COP Tj = -7°C

2.67

1.94

Cdh Tj = -7 °C

0.970

0.970

Pdh Tj = +2°C

30.80 kW

31.11 kW

COP Tj = +2°C

4.30

3.09

Cdh Tj = +2 °C

0.970

0.970

Pdh Tj = +7°C

35.10 kW

40.31 kW

COP Tj = +7°C

5.53

4.42

Cdh Tj = +7 °C

0.970

0.970

Pdh Tj = 12°C

40.91 kW

34.24 kW

COP Tj = 12°C

7.19

6.43

Cdh Tj = +12 °C

0.970

0.970

Pdh Tj = Tbiv

52.10 kW

53.00 kW

COP Tj = Tbiv

2.67

2.00

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

50.10 kW

48.62 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.50

1.57

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.970

0.970

WTOL

35 °C

55 °C

Poff

110 W

110 W

PTO

200 W

200 W

PSB

110 W

110 W

PCK

10 W

10 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

8.80 kW

14.01 kW

Annual energy consumption Qhe

28335 kWh

40595 kWh

WiSAN-YSE1 PRM-SC 30.2
Configure model
Model name
WiSAN-YSE1 PRM-SC 30.2
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

84.80 kW

El input

21.20 kW

COP

4.01

Average Climate

EN 12102-1

Sound power level outdoor

80 dB(A)

EN 14825

ηs

162 %

Prated

55.80 kW

SCOP

4.12

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

49.33 kW

COP Tj = -7°C

2.70

Cdh Tj = -7 °C

0.950

Pdh Tj = +2°C

31.45 kW

COP Tj = +2°C

4.15

Cdh Tj = +2 °C

0.950

Pdh Tj = +7°C

35.74 kW

COP Tj = +7°C

5.34

Cdh Tj = +7 °C

0.950

Pdh Tj = 12°C

41.42 kW

COP Tj = 12°C

6.68

Cdh Tj = +12 °C

0.950

Pdh Tj = Tbiv

49.33 kW

COP Tj = Tbiv

2.70

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

46.28 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.39

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.950

WTOL

35 °C

Poff

110 W

PTO

200 W

PSB

110 W

PCK

10 W

Supplementary Heater: Type of energy input

n/a

Supplementary Heater: PSUP

9.48 kW

Annual energy consumption Qhe

27961 kWh

WiSAN-YSE1 PRM-SC 35.2
Configure model
Model name
WiSAN-YSE1 PRM-SC 35.2
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

94.20 kW

El input

25.70 kW

COP

3.67

Average Climate

EN 12102-1

Sound power level outdoor

83 dB(A)

EN 14825

ηs

160 %

Prated

62.80 kW

SCOP

4.08

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

55.56 kW

COP Tj = -7°C

2.62

Cdh Tj = -7 °C

0.950

Pdh Tj = +2°C

33.51 kW

COP Tj = +2°C

4.10

Cdh Tj = +2 °C

0.950

Pdh Tj = +7°C

35.91 kW

COP Tj = +7°C

5.30

Cdh Tj = +7 °C

0.950

Pdh Tj = 12°C

42.87 kW

COP Tj = 12°C

6.60

Cdh Tj = +12 °C

0.950

Pdh Tj = Tbiv

55.56 kW

COP Tj = Tbiv

2.62

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

50.14 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.48

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.950

WTOL

35 °C

Poff

110 W

PTO

200 W

PSB

110 W

PCK

10 W

Supplementary Heater: Type of energy input

n/a

Supplementary Heater: PSUP

12.67 kW

Annual energy consumption Qhe

31806 kWh

WiSAN-YSE1 PRM-SC 40.2
Configure model
Model name
WiSAN-YSE1 PRM-SC 40.2
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

101.00 kW

El input

27.70 kW

COP

3.64

Average Climate

EN 12102-1

Sound power level outdoor

83 dB(A)

EN 14825

ηs

162 %

Prated

67.00 kW

SCOP

4.13

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

59.24 kW

COP Tj = -7°C

2.60

Cdh Tj = -7 °C

0.970

Pdh Tj = +2°C

36.53 kW

COP Tj = +2°C

4.08

Cdh Tj = +2 °C

0.970

Pdh Tj = +7°C

36.00 kW

COP Tj = +7°C

5.40

Cdh Tj = +7 °C

0.970

Pdh Tj = 12°C

42.95 kW

COP Tj = 12°C

6.76

Cdh Tj = +12 °C

0.970

Pdh Tj = Tbiv

59.24 kW

COP Tj = Tbiv

2.60

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

55.44 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.44

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.970

WTOL

35 °C

Poff

110 W

PTO

200 W

PSB

110 W

PCK

10 W

Supplementary Heater: Type of energy input

n/a

Supplementary Heater: PSUP

11.53 kW

Annual energy consumption Qhe

33528 kWh

WiSAN-YSE1 PRM-EN 30.2
Configure model
Model name
WiSAN-YSE1 PRM-EN 30.2
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

68.60 kW

El input

16.50 kW

COP

4.16

Average Climate

EN 12102-1

Sound power level outdoor

76 dB(A)

EN 14825

ηs

161 %

Prated

51.20 kW

SCOP

4.10

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

45.26 kW

COP Tj = -7°C

2.73

Cdh Tj = -7 °C

0.900

Pdh Tj = +2°C

27.20 kW

COP Tj = +2°C

4.23

Cdh Tj = +2 °C

0.900

Pdh Tj = +7°C

27.29 kW

COP Tj = +7°C

5.40

Cdh Tj = +7 °C

0.900

Pdh Tj = 12°C

40.91 kW

COP Tj = 12°C

6.70

Cdh Tj = +12 °C

0.900

Pdh Tj = Tbiv

45.26 kW

COP Tj = Tbiv

2.73

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

39.29 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.30

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

WTOL

35 °C

Poff

110 W

PTO

200 W

PSB

110 W

PCK

10 W

Supplementary Heater: Type of energy input

n/a

Supplementary Heater: PSUP

11.87 kW

Annual energy consumption Qhe

25750 kWh

WiSAN-YSE1 PRM-EN 35.2
Configure model
Model name
WiSAN-YSE1 PRM-EN 35.2
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

76.10 kW

El input

19.00 kW

COP

4.01

Average Climate

EN 12102-1

Sound power level outdoor

77 dB(A)

EN 14825

ηs

159 %

Prated

56.70 kW

SCOP

4.06

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

50.14 kW

COP Tj = -7°C

2.70

Cdh Tj = -7 °C

0.900

Pdh Tj = +2°C

30.53 kW

COP Tj = +2°C

4.11

Cdh Tj = +2 °C

0.900

Pdh Tj = +7°C

27.29 kW

COP Tj = +7°C

5.40

Cdh Tj = +7 °C

0.900

Pdh Tj = 12°C

40.91 kW

COP Tj = 12°C

6.70

Cdh Tj = +12 °C

0.900

Pdh Tj = Tbiv

50.14 kW

COP Tj = Tbiv

2.70

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

41.71 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.15

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

WTOL

35 °C

Poff

110 W

PTO

200 W

PSB

110 W

PCK

10 W

Supplementary Heater: Type of energy input

n/a

Supplementary Heater: PSUP

14.97 kW

Annual energy consumption Qhe

28860 kWh

WiSAN-YSE1 PRM-EN 40.2
Configure model
Model name
WiSAN-YSE1 PRM-EN 40.2
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

81.90 kW

El input

20.30 kW

COP

4.04

Average Climate

EN 12102-1

Sound power level outdoor

78 dB(A)

EN 14825

ηs

159 %

Prated

64.10 kW

SCOP

4.05

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

56.67 kW

COP Tj = -7°C

2.65

Cdh Tj = -7 °C

0.900

Pdh Tj = +2°C

33.07 kW

COP Tj = +2°C

4.08

Cdh Tj = +2 °C

0.900

Pdh Tj = +7°C

27.29 kW

COP Tj = +7°C

5.40

Cdh Tj = +7 °C

0.900

Pdh Tj = 12°C

40.91 kW

COP Tj = 12°C

6.70

Cdh Tj = +12 °C

0.900

Pdh Tj = Tbiv

56.67 kW

COP Tj = Tbiv

2.65

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

47.04 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.03

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

WTOL

35 °C

Poff

110 W

PTO

200 W

PSB

110 W

PCK

10 W

Supplementary Heater: Type of energy input

n/a

Supplementary Heater: PSUP

17.02 kW

Annual energy consumption Qhe

32639 kWh

WiSAN-YSE1 EXC-EN 30.2
Configure model
Model name
WiSAN-YSE1 EXC-EN 30.2
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

65.40 kW

60.00 kW

El input

15.50 kW

22.10 kW

COP

4.22

2.71

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

73 dB(A)

73 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

126 %

Prated

48.80 kW

47.71 kW

SCOP

4.24

3.22

Tbiv

-7 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

43.21 kW

39.44 kW

COP Tj = -7°C

2.67

2.00

Cdh Tj = -7 °C

0.970

0.970

Pdh Tj = +2°C

27.14 kW

29.50 kW

COP Tj = +2°C

4.32

3.15

Cdh Tj = +2 °C

0.970

0.970

Pdh Tj = +7°C

27.23 kW

39.10 kW

COP Tj = +7°C

5.40

4.42

Cdh Tj = +7 °C

0.970

0.970

Pdh Tj = 12°C

40.82 kW

33.11 kW

COP Tj = 12°C

6.70

6.15

Cdh Tj = +12 °C

0.970

0.970

Pdh Tj = Tbiv

43.21 kW

40.37 kW

COP Tj = Tbiv

2.67

2.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

38.45 kW

37.56 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.33

1.57

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.970

0.970

WTOL

35 °C

55 °C

Poff

110 W

110 W

PTO

200 W

200 W

PSB

110 W

110 W

PCK

10 W

10 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

10.40 kW

10.15 kW

Annual energy consumption Qhe

23799 kWh

30651 kWh

WiSAN-YSE1 EXC-EN 35.2
Configure model
Model name
WiSAN-YSE1 EXC-EN 35.2
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

72.70 kW

68.70 kW

El input

17.90 kW

25.90 kW

COP

4.07

2.65

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

75 dB(A)

75 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

165 %

125 %

Prated

52.60 kW

55.24 kW

SCOP

4.20

3.20

Tbiv

-7 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

46.55 kW

45.64 kW

COP Tj = -7°C

2.64

1.94

Cdh Tj = -7 °C

0.970

0.970

Pdh Tj = +2°C

28.48 kW

29.59 kW

COP Tj = +2°C

4.27

3.12

Cdh Tj = +2 °C

0.970

0.970

Pdh Tj = +7°C

27.37 kW

39.10 kW

COP Tj = +7°C

5.35

4.42

Cdh Tj = +7 °C

0.970

0.970

Pdh Tj = 12°C

41.05 kW

33.21 kW

COP Tj = 12°C

6.66

6.15

Cdh Tj = +12 °C

0.970

0.970

Pdh Tj = Tbiv

46.55 kW

46.74 kW

COP Tj = Tbiv

2.64

2.04

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

40.23 kW

41.48 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.30

1.57

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.970

0.970

WTOL

35 °C

55 °C

Poff

110 W

110 W

PTO

200 W

200 W

PSB

110 W

110 W

PCK

10 W

10 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

12.39 kW

13.76 kW

Annual energy consumption Qhe

25887 kWh

35690 kWh