1,200 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.60 kW
4.10 kW
El input
0.88 kW
1.55 kW
COP
5.20
2.65
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.25 kW
1.12 kW
Cooling capacity
4.50
6.00
EER
3.60
5.35
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
4.50 kW
6.00 kW
SEER
4.64
8.02
Pdc Tj = 35°C
4.50 kW
6.00 kW
EER Tj = 35°C
3.60
5.35
Pdc Tj = 30°C
3.32 kW
4.50 kW
EER Tj = 30°C
3.97
7.09
Cdc Tj = 30 °C
Pdc Tj = 25°C
2.30 kW
2.80 kW
EER Tj = 25°C
5.23
9.20
Cdc Tj = 25 °C
Pdc Tj = 20°C
1.85 kW
2.85 kW
EER Tj = 20°C
6.40
12.23
Cdc Tj = 20 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
582 kWh
449 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
32 dB(A)
32 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
234 %
163 %
Prated
5.00 kW
5.00 kW
SCOP
5.94
4.16
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
5.00 kW
5.00 kW
COP Tj = +2°C
3.51
2.42
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.30 kW
3.30 kW
COP Tj = +7°C
5.65
3.67
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
2.10 kW
1.90 kW
COP Tj = 12°C
7.94
5.67
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
5.00 kW
5.00 kW
COP Tj = Tbiv
3.51
2.42
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.00 kW
5.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.51
2.42
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
1125 kWh
1607 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
32 dB(A)
32 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
176 %
134 %
Prated
5.00 kW
5.00 kW
SCOP
4.48
3.43
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.40 kW
4.50 kW
COP Tj = -7°C
3.18
2.15
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.70 kW
2.70 kW
COP Tj = +2°C
4.44
3.39
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
1.75 kW
1.74 kW
COP Tj = +7°C
5.37
4.44
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
2.70 kW
2.10 kW
COP Tj = 12°C
8.78
7.29
Cdh Tj = +12 °C
0.95
0.95
Pdh Tj = Tbiv
5.00 kW
4.50 kW
COP Tj = Tbiv
3.00
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.00 kW
4.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.00
1.83
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0.7 kW
Annual energy consumption Qhe
2305 kWh
3009 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
169 %
COP
4.00
Heating up time
1:35 h:min
Standby power input
28.9 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
279 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
139 %
COP
3.30
Heating up time
1:35 h:min
Standby power input
31.8 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
279 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.60 kW
4.10 kW
El input
0.88 kW
1.55 kW
COP
5.20
2.65
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.25 kW
1.12 kW
Cooling capacity
4.50
6.00
EER
3.60
5.35
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
4.50 kW
6.00 kW
SEER
4.64
8.02
Pdc Tj = 35°C
4.50 kW
6.00 kW
EER Tj = 35°C
3.60
5.35
Pdc Tj = 30°C
3.32 kW
4.50 kW
EER Tj = 30°C
3.97
7.09
Pdc Tj = 25°C
2.30 kW
2.80 kW
EER Tj = 25°C
5.23
9.20
Pdc Tj = 20°C
1.85 kW
2.85 kW
EER Tj = 20°C
6.40
12.23
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
582 kWh
449 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
32 dB(A)
32 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
176 %
134 %
Prated
5.00 kW
5.00 kW
SCOP
4.48
3.43
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.40 kW
4.50 kW
COP Tj = -7°C
3.18
2.15
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.70 kW
2.70 kW
COP Tj = +2°C
4.44
3.39
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
1.75 kW
1.74 kW
COP Tj = +7°C
5.37
4.44
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
2.70 kW
2.10 kW
COP Tj = 12°C
8.78
7.29
Cdh Tj = +12 °C
0.95
0.95
Pdh Tj = Tbiv
5.00 kW
4.50 kW
COP Tj = Tbiv
3.00
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.00 kW
4.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.00
1.83
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0.7 kW
Annual energy consumption Qhe
2305 kWh
3009 kWh
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
234 %
163 %
Prated
5.00 kW
5.00 kW
SCOP
5.94
4.16
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
5.00 kW
5.00 kW
COP Tj = +2°C
3.51
2.42
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.30 kW
3.30 kW
COP Tj = +7°C
5.65
3.67
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
2.10 kW
1.90 kW
COP Tj = 12°C
7.94
5.67
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
5.00 kW
5.00 kW
COP Tj = Tbiv
3.51
2.42
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.00 kW
5.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.51
2.42
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
1125 kWh
1607 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
M
Efficiency ηDHW
131 %
COP
3.00
Heating up time
1:35 h:min
Standby power input
29.9 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
279 l
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
169 %
COP
4.00
Heating up time
1:35 h:min
Standby power input
28.9 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
279 l