Login

Subtype

HP20L-M-BC

Certificate Holder
Heliotherm GmbH
Sportplatzweg 18
A-6336 Langkampfen
Austria
Registration number
011-1W0205
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
HP20L-M-BC
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

9,300 kg

Certification Date
14.12.2017
Testing basis
HP KEYMARK certification scheme rules rev. 8
Generate PDF Export model CSV
  • Number of models 1

Models

HELIOTHERM - Luft-/Wasserwärmepumpe in Splittbauweise modulierend Baureihe Basic Comfort
Configure model
Model name
HELIOTHERM - Luft-/Wasserwärmepumpe in Splittbauweise modulierend Baureihe Basic Comfort
Application
Heating (low temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

16.15 kW

El input

3.01 kW

COP

5.37

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Sound power level indoor

43 dB(A)

Sound power level outdoor

46 dB(A)

EN 14825

ηs

262 %

Prated

18.00 kW

SCOP

6.56

Tbiv

2 °C

TOL

2 °C

Pdh Tj = +2°C

18.40 kW

COP Tj = +2°C

4.39

Cdh Tj = +2 °C

0.990

Pdh Tj = +7°C

11.35 kW

COP Tj = +7°C

6.16

Cdh Tj = +7 °C

0.990

Pdh Tj = 12°C

7.48 kW

COP Tj = 12°C

7.38

Cdh Tj = +12 °C

0.990

Pdh Tj = Tbiv

18.40 kW

COP Tj = Tbiv

4.39

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

18.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.39

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

WTOL

62 °C

Poff

1 W

PTO

7 W

PSB

7 W

PCK

6 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

4568 kWh

Colder Climate

EN 12102-1

Sound power level indoor

43 dB(A)

Sound power level outdoor

46 dB(A)

EN 14825

ηs

175 %

Prated

18.00 kW

SCOP

4.38

Tbiv

-18 °C

TOL

-22 °C

Pdh Tj = -7°C

11.20 kW

COP Tj = -7°C

3.70

Cdh Tj = -7 °C

0.990

Pdh Tj = +2°C

6.97 kW

COP Tj = +2°C

5.51

Cdh Tj = +2 °C

0.990

Pdh Tj = +7°C

6.39 kW

COP Tj = +7°C

6.13

Cdh Tj = +7 °C

0.990

Pdh Tj = 12°C

7.67 kW

COP Tj = 12°C

7.62

Cdh Tj = +12 °C

0.990

Pdh Tj = Tbiv

16.85 kW

COP Tj = Tbiv

2.27

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.90

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

WTOL

62 °C

Poff

1 W

PTO

7 W

PSB

7 W

PCK

6 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

3.95 kW

Annual energy consumption Qhe

8791 kWh

Pdh Tj = -15°C (if TOL<-20°C)

14.77

COP Tj = -15°C (if TOL<-20°C)

2.54

Cdh Tj = -15 °C

0.990

Average Climate

EN 12102-1

Sound power level indoor

43 dB(A)

Sound power level outdoor

46 dB(A)

EN 14825

ηs

205 %

Prated

18.00 kW

SCOP

5.21

Tbiv

-10 °C

TOL

-10 °C

Pdh Tj = -7°C

16.18 kW

COP Tj = -7°C

3.19

Cdh Tj = -7 °C

0.990

Pdh Tj = +2°C

9.20 kW

COP Tj = +2°C

5.22

Cdh Tj = +2 °C

0.990

Pdh Tj = +7°C

6.94 kW

COP Tj = +7°C

6.64

Cdh Tj = +7 °C

0.990

Pdh Tj = 12°C

8.13 kW

COP Tj = 12°C

7.64

Cdh Tj = +12 °C

0.990

Pdh Tj = Tbiv

18.47 kW

COP Tj = Tbiv

2.67

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

18.47 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.67

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

WTOL

62 °C

Poff

1 W

PTO

7 W

PSB

7 W

PCK

6 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

7100 kWh