6,600 kg
Heating
EN 14511-2
Heat output
7.99 kW
El input
1.70 kW
COP
4.71
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Sound power level outdoor
50 dB(A)
EN 14825
ηs
215 %
Prated
12.00 kW
SCOP
5.45
Tbiv
2 °C
TOL
2 °C
Pdh Tj = +2°C
11.91 kW
COP Tj = +2°C
4.30
Cdh Tj = +2 °C
0.990
Pdh Tj = +7°C
7.65 kW
COP Tj = +7°C
5.40
Cdh Tj = +7 °C
0.990
Pdh Tj = 12°C
5.42 kW
COP Tj = 12°C
5.73
Cdh Tj = +12 °C
0.990
Pdh Tj = Tbiv
11.91 kW
COP Tj = Tbiv
4.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.91 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
WTOL
62 °C
Poff
1 W
PTO
7 W
PSB
7 W
PCK
6 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.09 kW
Annual energy consumption Qhe
3083 kWh
Colder Climate
EN 12102-1
Sound power level outdoor
50 dB(A)
EN 14825
ηs
149 %
Prated
12.00 kW
SCOP
4.14
Tbiv
-19 °C
TOL
-22 °C
Pdh Tj = -7°C
7.17 kW
COP Tj = -7°C
3.45
Cdh Tj = -7 °C
0.990
Pdh Tj = +2°C
4.59 kW
COP Tj = +2°C
4.48
Cdh Tj = +2 °C
0.990
Pdh Tj = +7°C
4.61 kW
COP Tj = +7°C
4.85
Cdh Tj = +7 °C
0.990
Pdh Tj = 12°C
5.43 kW
COP Tj = 12°C
5.69
Cdh Tj = +12 °C
0.990
Pdh Tj = Tbiv
11.22 kW
COP Tj = Tbiv
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.61
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
WTOL
62 °C
Poff
1 W
PTO
7 W
PSB
7 W
PCK
6 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
2.60 kW
Annual energy consumption Qhe
6087 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.47
COP Tj = -15°C (if TOL<-20°C)
2.40
Cdh Tj = -15 °C
0.990
Average Climate
EN 12102-1
Sound power level outdoor
50 dB(A)
EN 14825
ηs
180 %
Prated
12.00 kW
SCOP
4.57
Tbiv
-10 °C
TOL
-10 °C
Pdh Tj = -7°C
10.62 kW
COP Tj = -7°C
2.72
Cdh Tj = -7 °C
0.997
Pdh Tj = +2°C
6.57 kW
COP Tj = +2°C
4.69
Cdh Tj = +2 °C
0.993
Pdh Tj = +7°C
7.48 kW
COP Tj = +7°C
5.64
Cdh Tj = +7 °C
0.987
Pdh Tj = 12°C
8.35 kW
COP Tj = 12°C
6.91
Cdh Tj = +12 °C
0.982
Pdh Tj = Tbiv
11.99 kW
COP Tj = Tbiv
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.99 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.20
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.998
WTOL
62 °C
Poff
1 W
PTO
7 W
PSB
7 W
PCK
6 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.01 kW
Annual energy consumption Qhe
5450 kWh