Login

Subtype

S08L-M-CC

Certificate Holder
Heliotherm GmbH
Sportplatzweg 18
A-6336 Langkampfen
Austria
Registration number
011-1W0477
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
S08L-M-CC
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

4,900 kg

Certification Date
14.12.2017
Testing basis
HP KEYMARK certification scheme rules rev. 8
Generate PDF Export model CSV
  • Number of models 1

Models

HELIOTHERM - Luft/Wasserwärmepumpe modulierend Baureihe Sensor Comfort Compact
Configure model
Model name
HELIOTHERM - Luft/Wasserwärmepumpe modulierend Baureihe Sensor Comfort Compact
Application
Heating (low temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

6.87 kW

El input

1.36 kW

COP

5.05

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Sound power level outdoor

48 dB(A)

EN 14825

ηs

230 %

Prated

10.00 kW

SCOP

5.82

Tbiv

2 °C

TOL

2 °C

Pdh Tj = +2°C

9.98 kW

COP Tj = +2°C

4.15

Cdh Tj = +2 °C

0.990

Pdh Tj = +7°C

6.42 kW

COP Tj = +7°C

5.68

Cdh Tj = +7 °C

0.990

Pdh Tj = 12°C

4.61 kW

COP Tj = 12°C

6.30

Cdh Tj = +12 °C

0.990

Pdh Tj = Tbiv

9.98 kW

COP Tj = Tbiv

4.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.98 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

WTOL

62 °C

Poff

1 W

PTO

7 W

PSB

7 W

PCK

6 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.02 kW

Annual energy consumption Qhe

2405 kWh

Colder Climate

EN 12102-1

Sound power level outdoor

48 dB(A)

EN 14825

ηs

159 %

Prated

10.00 kW

SCOP

4.05

Tbiv

-18 °C

TOL

-22 °C

Pdh Tj = -7°C

6.17 kW

COP Tj = -7°C

3.65

Cdh Tj = -7 °C

0.990

Pdh Tj = +2°C

3.75 kW

COP Tj = +2°C

4.81

Cdh Tj = +2 °C

0.990

Pdh Tj = +7°C

3.88 kW

COP Tj = +7°C

5.32

Cdh Tj = +7 °C

0.990

Pdh Tj = 12°C

4.67 kW

COP Tj = 12°C

6.36

Cdh Tj = +12 °C

0.990

Pdh Tj = Tbiv

8.87 kW

COP Tj = Tbiv

2.12

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.31

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

WTOL

62 °C

Poff

1 W

PTO

7 W

PSB

7 W

PCK

6 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

2.20 kW

Annual energy consumption Qhe

5185 kWh

Pdh Tj = -15°C (if TOL<-20°C)

8.18

COP Tj = -15°C (if TOL<-20°C)

2.37

Cdh Tj = -15 °C

0.990

Average Climate

EN 12102-1

Sound power level outdoor

48 dB(A)

EN 14825

ηs

177 %

Prated

10.00 kW

SCOP

4.49

Tbiv

-10 °C

TOL

-10 °C

Pdh Tj = -7°C

8.80 kW

COP Tj = -7°C

2.70

Cdh Tj = -7 °C

0.990

Pdh Tj = +2°C

5.47 kW

COP Tj = +2°C

4.55

Cdh Tj = +2 °C

0.990

Pdh Tj = +7°C

5.94 kW

COP Tj = +7°C

5.65

Cdh Tj = +7 °C

0.990

Pdh Tj = 12°C

6.71 kW

COP Tj = 12°C

7.03

Cdh Tj = +12 °C

0.990

Pdh Tj = Tbiv

10.15 kW

COP Tj = Tbiv

2.20

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.15 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.20

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

WTOL

62 °C

Poff

1 W

PTO

7 W

PSB

7 W

PCK

6 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

4600 kWh