Login

Subtype

HP08L-M-BC

Certificate Holder
Heliotherm GmbH
Sportplatzweg 18
A-6336 Langkampfen
Austria
Registration number
011-1W0203
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
HP08L-M-BC
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

7,400 kg

Certification Date
14.12.2017
Testing basis
HP KEYMARK certification scheme rules rev. 8
Generate PDF Export model CSV
  • Number of models 1

Models

HELIOTHERM - Luft-/Wasserwärmepumpe in Splittbauweise modulierend Baureihe Basic Comfort
Configure model
Model name
HELIOTHERM - Luft-/Wasserwärmepumpe in Splittbauweise modulierend Baureihe Basic Comfort
Application
Heating (low temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

10.22 kW

El input

1.92 kW

COP

5.33

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Sound power level indoor

40 dB(A)

Sound power level outdoor

40 dB(A)

EN 14825

ηs

241 %

Prated

10.00 kW

SCOP

6.10

Tbiv

2 °C

TOL

2 °C

Pdh Tj = +2°C

10.03 kW

COP Tj = +2°C

4.36

Cdh Tj = +2 °C

0.990

Pdh Tj = +7°C

6.45 kW

COP Tj = +7°C

5.96

Cdh Tj = +7 °C

0.990

Pdh Tj = 12°C

4.63 kW

COP Tj = 12°C

6.62

Cdh Tj = +12 °C

0.990

Pdh Tj = Tbiv

10.03 kW

COP Tj = Tbiv

4.36

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.03 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.36

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

WTOL

62 °C

Poff

1 W

PTO

7 W

PSB

7 W

PCK

6 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

2295 kWh

Colder Climate

EN 12102-1

Sound power level indoor

40 dB(A)

Sound power level outdoor

40 dB(A)

EN 14825

ηs

167 %

Prated

10.00 kW

SCOP

4.25

Tbiv

-18 °C

TOL

-22 °C

Pdh Tj = -7°C

6.20 kW

COP Tj = -7°C

3.83

Cdh Tj = -7 °C

0.990

Pdh Tj = +2°C

3.77 kW

COP Tj = +2°C

5.05

Cdh Tj = +2 °C

0.990

Pdh Tj = +7°C

3.90 kW

COP Tj = +7°C

5.59

Cdh Tj = +7 °C

0.990

Pdh Tj = 12°C

4.69 kW

COP Tj = 12°C

6.68

Cdh Tj = +12 °C

0.990

Pdh Tj = Tbiv

8.91 kW

COP Tj = Tbiv

2.23

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.84 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.38

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

WTOL

62 °C

Poff

1 W

PTO

7 W

PSB

7 W

PCK

6 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

2.16 kW

Annual energy consumption Qhe

4941 kWh

Pdh Tj = -15°C (if TOL<-20°C)

8.22

COP Tj = -15°C (if TOL<-20°C)

2.49

Cdh Tj = -15 °C

0.990

Average Climate

EN 12102-1

Sound power level indoor

40 dB(A)

Sound power level outdoor

40 dB(A)

EN 14825

ηs

185 %

Prated

10.00 kW

SCOP

4.71

Tbiv

-10 °C

TOL

-10 °C

Pdh Tj = -7°C

8.84 kW

COP Tj = -7°C

2.84

Cdh Tj = -7 °C

0.990

Pdh Tj = +2°C

5.50 kW

COP Tj = +2°C

4.78

Cdh Tj = +2 °C

0.990

Pdh Tj = +7°C

5.97 kW

COP Tj = +7°C

5.93

Cdh Tj = +7 °C

0.990

Pdh Tj = 12°C

6.74 kW

COP Tj = 12°C

7.38

Cdh Tj = +12 °C

0.990

Pdh Tj = Tbiv

10.20 kW

COP Tj = Tbiv

2.31

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.31

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

WTOL

62 °C

Poff

1 W

PTO

7 W

PSB

7 W

PCK

6 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

4400 kWh