5,600 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
17.60 kW
17.40 kW
El input
4.07 kW
5.58 kW
COP
4.33
3.11
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
152 %
125 %
Prated
20.70 kW
20.70 kW
SCOP
3.87
3.21
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
21.80 kW
22.20 kW
COP Tj = -7°C
3.02
2.36
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
14.30 kW
14.10 kW
COP Tj = +2°C
3.88
3.22
Cdh Tj = +2 °C
0.990
1.000
Pdh Tj = +7°C
18.00 kW
17.60 kW
COP Tj = +7°C
4.79
3.95
Cdh Tj = +7 °C
0.990
1.000
Pdh Tj = 12°C
21.90 kW
21.30 kW
COP Tj = 12°C
5.72
4.93
Cdh Tj = +12 °C
0.990
1.000
Pdh Tj = Tbiv
20.50 kW
20.60 kW
COP Tj = Tbiv
2.90
2.17
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
20.50 kW
20.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.90
2.17
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
20 W
20 W
PTO
20 W
20 W
PSB
20 W
20 W
PCK
88 W
88 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.20 kW
0.10 kW
Annual energy consumption Qhe
11198 kWh
13342 kWh