Login

Subtype

FDCW60VNX-W

Certificate Holder
Mitsubishi Heavy Industries Air Conditioning Europe
5 The Square
UB11 1ET Uxbridge, Middlesex
United Kingdom
Registration number
012-C700109 / Issue 1
Certification Body
RISE CERT
Subtype title
FDCW60VNX-W
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,300 kg

Certification Date
13.09.2021
Testing basis
EN 14511:2018, EN 14825:2018, EN 12102:2017
Generate PDF Export model CSV Download certificate
  • Number of models 1

Models

FDCW60VNX-W + HSB60-W
Configure model
Model name
FDCW60VNX-W + HSB60-W
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.08 kW

4.16 kW

El input

0.99 kW

1.36 kW

COP

5.16

3.06

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

33 dB(A)

33 dB(A)

Sound power level outdoor

52 dB(A)

52 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

190 %

137 %

Prated

4.80 kW

5.30 kW

SCOP

4.75

3.44

Tbiv

-10 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.20 kW

4.80 kW

COP Tj = -7°C

3.06

1.95

Cdh Tj = -7 °C

0.980

0.990

Pdh Tj = +2°C

2.60 kW

2.90 kW

COP Tj = +2°C

4.61

3.37

Cdh Tj = +2 °C

0.980

0.990

Pdh Tj = +7°C

1.70 kW

1.90 kW

COP Tj = +7°C

6.18

4.63

Cdh Tj = +7 °C

0.980

0.990

Pdh Tj = 12°C

2.70 kW

2.60 kW

COP Tj = 12°C

7.96

6.14

Cdh Tj = +12 °C

0.980

0.990

Pdh Tj = Tbiv

4.80 kW

4.80 kW

COP Tj = Tbiv

2.24

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.80 kW

4.60 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.24

1.94

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.980

0.990

WTOL

58 °C

58 °C

Poff

7 W

7 W

PTO

12 W

12 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.70 kW

Annual energy consumption Qhe

2089 kWh

3193 kWh