1,300 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.08 kW
4.16 kW
El input
0.99 kW
1.36 kW
COP
5.16
3.06
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
33 dB(A)
33 dB(A)
Sound power level outdoor
52 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
137 %
Prated
4.80 kW
5.30 kW
SCOP
4.75
3.44
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.20 kW
4.80 kW
COP Tj = -7°C
3.06
1.95
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
2.60 kW
2.90 kW
COP Tj = +2°C
4.61
3.37
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
1.70 kW
1.90 kW
COP Tj = +7°C
6.18
4.63
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
2.70 kW
2.60 kW
COP Tj = 12°C
7.96
6.14
Cdh Tj = +12 °C
0.980
0.990
Pdh Tj = Tbiv
4.80 kW
4.80 kW
COP Tj = Tbiv
2.24
1.95
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.80 kW
4.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.24
1.94
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.980
0.990
WTOL
58 °C
58 °C
Poff
7 W
7 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.70 kW
Annual energy consumption Qhe
2089 kWh
3193 kWh