2,200 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
13.6 kW
11.4 kW
El input
2.59 kW
3.53 kW
COP
5.25
3.23
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
60.8 dB(A)
60.8 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
215 %
160 %
Prated
10.00 kW
10.00 kW
SCOP
5.46
4.08
Tbiv
-8 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.60 kW
9.68 kW
COP Tj = -7°C
3.03
2.16
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
6.09 kW
6.05 kW
COP Tj = +2°C
6.20
3.92
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
4.30 kW
4.14 kW
COP Tj = +7°C
8.50
8.62
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
4.10 kW
4.11 kW
COP Tj = 12°C
10.30
8.62
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.14 kW
8.91 kW
COP Tj = Tbiv
3.02
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.69 kW
7.36 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.98
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
60 °C
60 °C
Poff
100 W
100 W
PTO
40 W
40 W
PSB
100 W
100 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.31 kW
2.64 kW
Annual energy consumption Qhe
3787 kWh
5066 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
113 %
COP
2.74
Heating up time
01:03 h:min
Standby power input
26.3 W
Reference hot water temperature
49.99 °C
Mixed water at 40°C
287 l