Login

Subtype

BHP 080 100 W

Certificate Holder
AERMEC S.p.A.
Via Roma 996
37040 Bevilacqua (VR)
Italy
Registration number
041-K011-09
Certification Body
BRE Global Limited
Subtype title
BHP 080 100 W
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,600 kg

Certification Date
30.07.2021
Testing basis
HP Keymark Scheme Rules Rev 08
Generate PDF Export model CSV Download certificate
  • Number of models 2

Models

BHP 080 + BHP 100 W
Configure model
Model name
BHP 080 + BHP 100 W
Application
Heating + DHW
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Medium temperature

Heat output

7.98 kW

El input

2.60 kW

COP

3.06

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Medium temperature

Sound power level indoor

42 dB(A)

Sound power level outdoor

67 dB(A)

EN 14825

Medium temperature

ηs

129 %

Prated

7.00 kW

SCOP

3.31

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

6.34 kW

COP Tj = -7°C

2.24

Cdh Tj = -7 °C

0.99

Pdh Tj = +2°C

4.08 kW

COP Tj = +2°C

3.18

Cdh Tj = +2 °C

0.98

Pdh Tj = +7°C

4.26 kW

COP Tj = +7°C

4.26

Cdh Tj = +7 °C

0.97

Pdh Tj = 12°C

5.01 kW

COP Tj = 12°C

5.93

Cdh Tj = +12 °C

0.97

Pdh Tj = Tbiv

6.34 kW

COP Tj = Tbiv

2.24

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.29 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.79

WTOL

60 °C

Poff

25 W

PTO

25 W

PSB

25 W

PCK

25 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.70 kW

Annual energy consumption Qhe

4371 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

116 %

COP

2.76

Heating up time

2.7 h:min

Standby power input

54.5 W

Reference hot water temperature

52.8 °C

Mixed water at 40°C

341 l

BHP 100 + BHP 100 W
Configure model
Model name
BHP 100 + BHP 100 W
Application
Heating + DHW
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Medium temperature

Heat output

9.47 kW

El input

3.12 kW

COP

3.04

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Medium temperature

Sound power level indoor

42 dB(A)

Sound power level outdoor

68 dB(A)

EN 14825

Medium temperature

ηs

127 %

Prated

8.00 kW

SCOP

3.25

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

6.91 kW

COP Tj = -7°C

2.12

Cdh Tj = -7 °C

0.99

Pdh Tj = +2°C

4.22 kW

COP Tj = +2°C

3.09

Cdh Tj = +2 °C

0.98

Pdh Tj = +7°C

4.27 kW

COP Tj = +7°C

4.34

Cdh Tj = +7 °C

0.97

Pdh Tj = 12°C

4.91 kW

COP Tj = 12°C

5.91

Cdh Tj = +12 °C

0.97

Pdh Tj = Tbiv

6.91 kW

COP Tj = Tbiv

2.12

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.85 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.75

WTOL

60 °C

Poff

25 W

PTO

25 W

PSB

25 W

PCK

25 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

1.20 kW

Annual energy consumption Qhe

5091 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

116 %

COP

2.76

Heating up time

2.7 h:min

Standby power input

54.5 W

Reference hot water temperature

52.8 °C

Mixed water at 40°C

341 l