1,550 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
11.1 kW
10.5 kW
El input
2.1 kW
3.358 kW
COP
5.28
3.12
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64.1 dB(A)
64.1 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
207 %
138 %
Prated
9.20 kW
8.70 kW
SCOP
5.24
3.53
Tbiv
-8 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.03 kW
8.16 kW
COP Tj = -7°C
3.30
2.29
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
5.29 kW
5.07 kW
COP Tj = +2°C
5.96
3.53
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
3.40 kW
3.40 kW
COP Tj = +7°C
7.80
5.41
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
3.70 kW
3.95 kW
COP Tj = 12°C
9.20
8.45
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
8.49 kW
8.03 kW
COP Tj = Tbiv
3.11
2.14
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.90 kW
5.77 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.74
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
60 °C
60 °C
Poff
100 W
100 W
PTO
40 W
40 W
PSB
100 W
100 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.30 kW
2.93 kW
Annual energy consumption Qhe
3628 kWh
5085 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
100 %
COP
2.40
Heating up time
1:26 h:min
Standby power input
31.3 W
Reference hot water temperature
51.6 °C
Mixed water at 40°C
305 l