Login

Subtype

Grant Aerona3 HPID6R32

Certificate Holder
Grant Engineering (Ireland) ULC
Barrack St
R42 D788 Ballinree, Birr
Ireland
Registration number
041-K005-01
Certification Body
BRE Global Limited
Subtype title
Grant Aerona3 HPID6R32
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

0,800 kg

Certification Date
01.03.2022
Testing basis
Heat Pump Keymark Scheme Rules Rev 09
Generate PDF Export model CSV Download certificate
  • Number of models 1

Models

HPID6R32
Configure model
Model name
HPID6R32
Application
Heating + DHW + low temp
Units
Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.92 kW

6.24 kW

El input

1.41 kW

2.05 kW

COP

4.91

3.04

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

65.2 dB(A)

65.2 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

185 %

132 %

Prated

4.50 kW

4.50 kW

SCOP

4.70

3.38

Tbiv

-9 °C

-9 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.68 kW

5.03 kW

COP Tj = -7°C

3.13

2.11

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

3.24 kW

3.21 kW

COP Tj = +2°C

6.02

4.03

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

2.10 kW

2.20 kW

COP Tj = +7°C

7.40

5.10

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

2.00 kW

1.78 kW

COP Tj = 12°C

9.20

6.15

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

4.50 kW

4.49 kW

COP Tj = Tbiv

3.02

1.99

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.87 kW

3.51 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.67

1.85

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

0.990

WTOL

60 °C

60 °C

Poff

100 W

100 W

PTO

40 W

40 W

PSB

100 W

100 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.63 kW

0.99 kW

Annual energy consumption Qhe

1979 kWh

2754 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

114 %

COP

2.75

Heating up time

1:47 h:min

Standby power input

26.3 W

Reference hot water temperature

49.0 °C

Mixed water at 40°C

278 l