0,800 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.92 kW
6.24 kW
El input
1.41 kW
2.05 kW
COP
4.91
3.04
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
65.2 dB(A)
65.2 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
132 %
Prated
4.50 kW
4.50 kW
SCOP
4.70
3.38
Tbiv
-9 °C
-9 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.68 kW
5.03 kW
COP Tj = -7°C
3.13
2.11
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
3.24 kW
3.21 kW
COP Tj = +2°C
6.02
4.03
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
2.10 kW
2.20 kW
COP Tj = +7°C
7.40
5.10
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
2.00 kW
1.78 kW
COP Tj = 12°C
9.20
6.15
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
4.50 kW
4.49 kW
COP Tj = Tbiv
3.02
1.99
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.87 kW
3.51 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
60 °C
60 °C
Poff
100 W
100 W
PTO
40 W
40 W
PSB
100 W
100 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.63 kW
0.99 kW
Annual energy consumption Qhe
1979 kWh
2754 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
114 %
COP
2.75
Heating up time
1:47 h:min
Standby power input
26.3 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
278 l