Login

Subtype

HMI160 / DHWT300

Certificate Holder
AERMEC S.p.A.
Via Roma 996
37040 Bevilacqua (VR)
Italy
Registration number
041-K011-07
Certification Body
BRE Global Limited
Subtype title
HMI160 / DHWT300
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

2,200 kg

Certification Date
25.03.2021
Testing basis
Heat Pump Keymark Scheme Rules Rev 08
Generate PDF Export model CSV Download certificate
  • Number of models 2

Models

HMI160 / DHWT300X
Configure model
Model name
HMI160 / DHWT300X
Application
Heating + DHW
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Medium temperature

Heat output

16.71 kW

El input

5.90 kW

COP

2.83

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Medium temperature

Sound power level outdoor

72 dB(A)

EN 14825

Medium temperature

ηs

126 %

Prated

13.00 kW

SCOP

3.24

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

11.98 kW

COP Tj = -7°C

2.05

Cdh Tj = -7 °C

0.98

Pdh Tj = +2°C

7.41 kW

COP Tj = +2°C

3.19

Cdh Tj = +2 °C

0.98

Pdh Tj = +7°C

5.70 kW

COP Tj = +7°C

4.18

Cdh Tj = +7 °C

0.98

Pdh Tj = 12°C

6.38 kW

COP Tj = 12°C

5.14

Cdh Tj = +12 °C

0.98

Pdh Tj = Tbiv

11.98 kW

COP Tj = Tbiv

2.05

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.41 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.78

WTOL

55 °C

Poff

18 W

PTO

18 W

PSB

18 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

2.59 kW

Annual energy consumption Qhe

8292 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

110 %

COP

2.62

Heating up time

1:52 h:min

Standby power input

62.6 W

Reference hot water temperature

52.8 °C

Mixed water at 40°C

372 l

HMI160T / DHWT300XT
Configure model
Model name
HMI160T / DHWT300XT
Application
Heating + DHW
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Medium temperature

Heat output

16.71 kW

El input

5.90 kW

COP

2.83

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Medium temperature

Sound power level outdoor

72 dB(A)

EN 14825

Medium temperature

ηs

126 %

Prated

13.00 kW

SCOP

3.24

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

11.98 kW

COP Tj = -7°C

2.05

Cdh Tj = -7 °C

0.98

Pdh Tj = +2°C

7.41 kW

COP Tj = +2°C

3.19

Cdh Tj = +2 °C

0.98

Pdh Tj = +7°C

5.70 kW

COP Tj = +7°C

4.18

Cdh Tj = +7 °C

0.98

Pdh Tj = 12°C

6.38 kW

COP Tj = 12°C

5.14

Cdh Tj = +12 °C

0.98

Pdh Tj = Tbiv

11.98 kW

COP Tj = Tbiv

2.05

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.41 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.78

WTOL

55 °C

Poff

18 W

PTO

18 W

PSB

18 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

2.59 kW

Annual energy consumption Qhe

8292 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

110 %

COP

2.62

Heating up time

1:52 h:min

Standby power input

62.6 W

Reference hot water temperature

52.8 °C

Mixed water at 40°C

372 l