Aqua thermal 90kW

Certificate Holder
GD Midea Heating & Ventilating Equipment Co., Ltd.
Penglai Industry Road
528311 Beijiao, Shunde, Foshan
China
Registration number
041-K007-12 / 1
Certification Body
BRE Global Limited
Subtype title
Aqua thermal 90kW
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

16,000 kg

Certification Date
24.08.2021
Testing basis
HP Keymark Scheme Rules Rev 08
Generate PDF Export model CSV Download certificate
  • Number of models 2

Models

MC-SU90-RN8L-B
Configure model
Model name
MC-SU90-RN8L-B
Application
Heating (low temp)
Units
n/a
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

90.00 kW

El input

23.30 kW

COP

3.87

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 14825

ηs

175 %

Prated

63.87 kW

SCOP

4.46

Tbiv

7 °C

TOL

2 °C

Pdh Tj = +2°C

63.87 kW

COP Tj = +2°C

2.64

Cdh Tj = +2 °C

0.90

Pdh Tj = +7°C

42.10 kW

COP Tj = +7°C

4.36

Cdh Tj = +7 °C

0.90

Pdh Tj = 12°C

28.30 kW

COP Tj = 12°C

5.47

Cdh Tj = +12 °C

0.90

Pdh Tj = Tbiv

42.10 kW

COP Tj = Tbiv

4.36

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

63.87 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.64

WTOL

54 °C

Poff

90 W

PTO

700 W

PSB

90 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

19137 kWh

Colder Climate

EN 14825

ηs

121 %

Prated

61.42 kW

SCOP

3.11

Tbiv

-15 °C

TOL

-20 °C

Pdh Tj = -7°C

37.64 kW

COP Tj = -7°C

2.92

Cdh Tj = -7 °C

0.900

Pdh Tj = +2°C

22.32 kW

COP Tj = +2°C

3.46

Cdh Tj = +2 °C

0.900

Pdh Tj = +7°C

25.15 kW

COP Tj = +7°C

4.68

Cdh Tj = +7 °C

0.900

Pdh Tj = 12°C

27.59 kW

COP Tj = 12°C

5.41

Cdh Tj = +12 °C

0.900

Pdh Tj = Tbiv

50.11 kW

COP Tj = Tbiv

2.09

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

38.35 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.73

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

WTOL

54 °C

Poff

90 W

PTO

700 W

PSB

90 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

61.42 kW

Annual energy consumption Qhe

48714 kWh

Pdh Tj = -15°C (if TOL<-20°C)

50.11

COP Tj = -15°C (if TOL<-20°C)

2.09

Cdh Tj = -15 °C

0.900

Average Climate

EN 14825

ηs

155 %

Prated

77.10 kW

SCOP

3.97

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

68.21 kW

COP Tj = -7°C

2.49

Cdh Tj = -7 °C

0.90

Pdh Tj = +2°C

43.18 kW

COP Tj = +2°C

3.78

Cdh Tj = +2 °C

0.90

Pdh Tj = +7°C

27.65 kW

COP Tj = +7°C

5.63

Cdh Tj = +7 °C

0.90

Pdh Tj = 12°C

28.53 kW

COP Tj = 12°C

5.70

Cdh Tj = +12 °C

0.90

Pdh Tj = Tbiv

68.21 kW

COP Tj = Tbiv

2.49

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

71.09 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

WTOL

54 °C

Poff

90 W

PTO

700 W

PSB

90 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

6.01 kW

Annual energy consumption Qhe

40075 kWh

MC-SU90M-RN8L-B
Configure model
Model name
MC-SU90M-RN8L-B
Application
Heating (low temp)
Units
n/a
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

90.00 kW

El input

29.52 kW

COP

3.06

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 14825

ηs

114 %

Prated

63.97 kW

SCOP

2.93

Tbiv

7 °C

TOL

2 °C

Pdh Tj = +2°C

63.97 kW

COP Tj = +2°C

2.17

Cdh Tj = +2 °C

0.90

Pdh Tj = +7°C

40.84 kW

COP Tj = +7°C

2.81

Cdh Tj = +7 °C

0.90

Pdh Tj = 12°C

28.70 kW

COP Tj = 12°C

3.47

Cdh Tj = +12 °C

0.90

Pdh Tj = Tbiv

40.84 kW

COP Tj = Tbiv

2.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

63.97 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.17

WTOL

54 °C

Poff

90 W

PTO

700 W

PSB

90 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

29169 kWh

Colder Climate

EN 14825

ηs

99 %

Prated

58.94 kW

SCOP

2.56

Tbiv

-15 °C

TOL

-20 °C

Pdh Tj = -7°C

36.13 kW

COP Tj = -7°C

2.62

Cdh Tj = -7 °C

0.90

Pdh Tj = +2°C

22.38 kW

COP Tj = +2°C

2.78

Cdh Tj = +2 °C

0.90

Pdh Tj = +7°C

24.41 kW

COP Tj = +7°C

3.02

Cdh Tj = +7 °C

0.90

Pdh Tj = 12°C

27.98 kW

COP Tj = 12°C

3.43

Cdh Tj = +12 °C

0.90

Pdh Tj = Tbiv

48.08 kW

COP Tj = Tbiv

1.90

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

36.81 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.57

WTOL

54 °C

Poff

90 W

PTO

700 W

PSB

90 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

58.94 kW

Annual energy consumption Qhe

56780 kWh

Pdh Tj = -15°C (if TOL<-20°C)

48.08

COP Tj = -15°C (if TOL<-20°C)

1.90

Cdh Tj = -15 °C

0.90

Average Climate

EN 14825

ηs

147 %

Prated

74.30 kW

SCOP

3.77

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

65.41 kW

COP Tj = -7°C

2.45

Cdh Tj = -7 °C

0.90

Pdh Tj = +2°C

43.01 kW

COP Tj = +2°C

3.63

Cdh Tj = +2 °C

0.90

Pdh Tj = +7°C

26.42 kW

COP Tj = +7°C

5.08

Cdh Tj = +7 °C

0.90

Pdh Tj = 12°C

28.54 kW

COP Tj = 12°C

5.94

Cdh Tj = +12 °C

0.90

Pdh Tj = Tbiv

65.41 kW

COP Tj = Tbiv

2.45

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

71.03 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.32

WTOL

54 °C

Poff

90 W

PTO

700 W

PSB

90 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

3.27 kW

Annual energy consumption Qhe

40747 kWh