2,500 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
11.50 kW
9.86 kW
El input
2.45 kW
3.52 kW
COP
4.70
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
8.90 kW
ηs
160 %
113 %
Prated
9.20 kW
8.90 kW
SCOP
4.08
2.90
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.15 kW
7.84 kW
COP Tj = -7°C
2.88
1.93
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.17 kW
5.54 kW
COP Tj = +2°C
3.93
2.76
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.99 kW
9.25 kW
COP Tj = +7°C
5.31
3.89
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
7.44 kW
6.77 kW
COP Tj = 12°C
7.15
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.15 kW
7.84 kW
COP Tj = Tbiv
2.88
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.46 kW
7.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.84
1.74
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.75 kW
1.84 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
19044 kWh
18303 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
11.50 kW
9.86 kW
El input
2.45 kW
3.52 kW
COP
4.70
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
8.90 kW
ηs
160 %
113 %
Prated
9.20 kW
8.90 kW
SCOP
4.08
2.90
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.15 kW
7.84 kW
COP Tj = -7°C
2.88
1.93
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.17 kW
5.54 kW
COP Tj = +2°C
3.93
2.76
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.99 kW
9.25 kW
COP Tj = +7°C
5.31
3.89
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
7.44 kW
6.77 kW
COP Tj = 12°C
7.15
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.15 kW
7.84 kW
COP Tj = Tbiv
2.88
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.46 kW
7.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.84
1.74
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.75 kW
1.84 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
19044 kWh
18303 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
11.50 kW
9.86 kW
El input
2.45 kW
3.52 kW
COP
4.70
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
8.90 kW
ηs
160 %
113 %
Prated
9.20 kW
8.90 kW
SCOP
4.08
2.90
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.15 kW
7.84 kW
COP Tj = -7°C
2.88
1.93
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.17 kW
5.54 kW
COP Tj = +2°C
3.93
2.76
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.99 kW
9.25 kW
COP Tj = +7°C
5.31
3.89
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
7.44 kW
6.77 kW
COP Tj = 12°C
7.15
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.15 kW
7.84 kW
COP Tj = Tbiv
2.88
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.46 kW
7.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.84
1.74
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.75 kW
1.84 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
19044 kWh
18303 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
11.50 kW
9.86 kW
El input
2.45 kW
3.52 kW
COP
4.70
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
8.90 kW
ηs
160 %
113 %
Prated
9.20 kW
8.90 kW
SCOP
4.08
2.90
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.15 kW
7.84 kW
COP Tj = -7°C
2.88
1.93
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.17 kW
5.54 kW
COP Tj = +2°C
3.93
2.76
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.99 kW
9.25 kW
COP Tj = +7°C
5.31
3.89
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
7.44 kW
6.77 kW
COP Tj = 12°C
7.15
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.15 kW
7.84 kW
COP Tj = Tbiv
2.88
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.46 kW
7.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.84
1.74
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.75 kW
1.84 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
19044 kWh
18303 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
11.50 kW
9.86 kW
El input
2.45 kW
3.52 kW
COP
4.70
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
8.90 kW
ηs
160 %
113 %
Prated
9.20 kW
8.90 kW
SCOP
4.08
2.90
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.15 kW
7.84 kW
COP Tj = -7°C
2.88
1.93
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.17 kW
5.54 kW
COP Tj = +2°C
3.93
2.76
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.99 kW
9.25 kW
COP Tj = +7°C
5.31
3.89
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
7.44 kW
6.77 kW
COP Tj = 12°C
7.15
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.15 kW
7.84 kW
COP Tj = Tbiv
2.88
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.46 kW
7.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.84
1.74
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.75 kW
1.84 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
19044 kWh
18303 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
124 %
COP
2.55
Heating up time
0:58 h:min
Standby power input
35.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
290 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
11.50 kW
9.86 kW
El input
2.45 kW
3.52 kW
COP
4.70
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
8.90 kW
ηs
160 %
113 %
Prated
9.20 kW
8.90 kW
SCOP
4.08
2.90
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.15 kW
7.84 kW
COP Tj = -7°C
2.88
1.93
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.17 kW
5.54 kW
COP Tj = +2°C
3.93
2.76
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.99 kW
9.25 kW
COP Tj = +7°C
5.31
3.89
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
7.44 kW
6.77 kW
COP Tj = 12°C
7.15
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.15 kW
7.84 kW
COP Tj = Tbiv
2.88
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.46 kW
7.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.84
1.74
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.75 kW
1.84 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
19044 kWh
18303 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
124 %
COP
2.55
Heating up time
0:58 h:min
Standby power input
35.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
290 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
11.50 kW
9.86 kW
El input
2.45 kW
3.52 kW
COP
4.70
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
8.90 kW
ηs
160 %
113 %
Prated
9.20 kW
8.90 kW
SCOP
4.08
2.90
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.15 kW
7.84 kW
COP Tj = -7°C
2.88
1.93
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.17 kW
5.54 kW
COP Tj = +2°C
3.93
2.76
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.99 kW
9.25 kW
COP Tj = +7°C
5.31
3.89
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
7.44 kW
6.77 kW
COP Tj = 12°C
7.15
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.15 kW
7.84 kW
COP Tj = Tbiv
2.88
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.46 kW
7.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.84
1.74
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.75 kW
1.84 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
19044 kWh
18303 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
124 %
COP
2.55
Heating up time
0:58 h:min
Standby power input
35.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
290 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
11.50 kW
9.86 kW
El input
2.45 kW
3.52 kW
COP
4.70
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
8.90 kW
ηs
160 %
113 %
Prated
9.20 kW
8.90 kW
SCOP
4.08
2.90
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.15 kW
7.84 kW
COP Tj = -7°C
2.88
1.93
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.17 kW
5.54 kW
COP Tj = +2°C
3.93
2.76
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.99 kW
9.25 kW
COP Tj = +7°C
5.31
3.89
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
7.44 kW
6.77 kW
COP Tj = 12°C
7.15
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.15 kW
7.84 kW
COP Tj = Tbiv
2.88
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.46 kW
7.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.84
1.74
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.75 kW
1.84 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
19044 kWh
18303 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
124 %
COP
2.55
Heating up time
0:58 h:min
Standby power input
35.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
290 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
13.50 kW
11.82 kW
El input
2.89 kW
4.23 kW
COP
4.67
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
10.70 kW
ηs
160 %
117 %
Prated
9.90 kW
10.70 kW
SCOP
4.08
3.00
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.73 kW
9.44 kW
COP Tj = -7°C
2.86
2.05
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.34 kW
6.11 kW
COP Tj = +2°C
3.92
2.82
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.99 kW
9.33 kW
COP Tj = +7°C
5.31
4.03
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
7.44 kW
6.77 kW
COP Tj = 12°C
7.15
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.73 kW
9.44 kW
COP Tj = Tbiv
2.86
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.46 kW
6.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.42
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.41 kW
3.86 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
20384 kWh
22040 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
13.50 kW
11.82 kW
El input
2.89 kW
4.23 kW
COP
4.67
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
10.70 kW
ηs
160 %
117 %
Prated
9.90 kW
10.70 kW
SCOP
4.08
3.00
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.73 kW
9.44 kW
COP Tj = -7°C
2.86
2.05
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.34 kW
6.11 kW
COP Tj = +2°C
3.92
2.82
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.99 kW
9.33 kW
COP Tj = +7°C
5.31
4.03
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
7.44 kW
6.77 kW
COP Tj = 12°C
7.15
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.73 kW
9.44 kW
COP Tj = Tbiv
2.86
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.46 kW
6.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.42
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.41 kW
3.86 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
20384 kWh
22040 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
13.50 kW
11.82 kW
El input
2.89 kW
4.23 kW
COP
4.67
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
10.70 kW
ηs
160 %
117 %
Prated
9.90 kW
10.70 kW
SCOP
4.08
3.00
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.73 kW
9.44 kW
COP Tj = -7°C
2.86
2.05
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.34 kW
6.11 kW
COP Tj = +2°C
3.92
2.82
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.99 kW
9.33 kW
COP Tj = +7°C
5.31
4.03
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
7.44 kW
6.77 kW
COP Tj = 12°C
7.15
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.73 kW
9.44 kW
COP Tj = Tbiv
2.86
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.46 kW
6.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.42
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.41 kW
3.86 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
20384 kWh
22040 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
13.50 kW
11.82 kW
El input
2.89 kW
4.23 kW
COP
4.67
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
10.70 kW
ηs
160 %
117 %
Prated
9.90 kW
10.70 kW
SCOP
4.08
3.00
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.73 kW
9.44 kW
COP Tj = -7°C
2.86
2.05
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.34 kW
6.11 kW
COP Tj = +2°C
3.92
2.82
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.99 kW
9.33 kW
COP Tj = +7°C
5.31
4.03
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
7.44 kW
6.77 kW
COP Tj = 12°C
7.15
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.73 kW
9.44 kW
COP Tj = Tbiv
2.86
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.46 kW
6.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.42
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.41 kW
3.86 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
20384 kWh
22040 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
13.50 kW
11.82 kW
El input
2.89 kW
4.23 kW
COP
4.67
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
10.70 kW
ηs
160 %
117 %
Prated
9.90 kW
10.70 kW
SCOP
4.08
3.00
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.73 kW
9.44 kW
COP Tj = -7°C
2.86
2.05
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.34 kW
6.11 kW
COP Tj = +2°C
3.92
2.82
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.99 kW
9.33 kW
COP Tj = +7°C
5.31
4.03
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
7.44 kW
6.77 kW
COP Tj = 12°C
7.15
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.73 kW
9.44 kW
COP Tj = Tbiv
2.86
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.46 kW
6.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.42
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
20384 kWh
22040 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
124 %
COP
2.55
Heating up time
0:58 h:min
Standby power input
35.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
290 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
13.50 kW
11.82 kW
El input
2.89 kW
4.23 kW
COP
4.67
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
10.70 kW
ηs
160 %
117 %
Prated
9.90 kW
10.70 kW
SCOP
4.08
3.00
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.73 kW
9.44 kW
COP Tj = -7°C
2.86
2.05
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.34 kW
6.11 kW
COP Tj = +2°C
3.92
2.82
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.99 kW
9.33 kW
COP Tj = +7°C
5.31
4.03
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
7.44 kW
6.77 kW
COP Tj = 12°C
7.15
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.73 kW
9.44 kW
COP Tj = Tbiv
2.86
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.46 kW
6.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.42
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.41 kW
3.86 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
20384 kWh
22040 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
124 %
COP
2.55
Heating up time
0:58 h:min
Standby power input
35.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
290 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
13.50 kW
11.82 kW
El input
2.89 kW
4.23 kW
COP
4.67
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
10.70 kW
ηs
160 %
117 %
Prated
9.90 kW
10.70 kW
SCOP
4.08
3.00
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.73 kW
9.44 kW
COP Tj = -7°C
2.86
2.05
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.34 kW
6.11 kW
COP Tj = +2°C
3.92
2.82
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.99 kW
9.33 kW
COP Tj = +7°C
5.31
4.03
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
7.44 kW
6.77 kW
COP Tj = 12°C
7.15
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.73 kW
9.44 kW
COP Tj = Tbiv
2.86
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.46 kW
6.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.42
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.41 kW
3.86 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
20384 kWh
22040 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
124 %
COP
2.55
Heating up time
0:58 h:min
Standby power input
35.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
290 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
13.50 kW
11.82 kW
El input
2.89 kW
4.23 kW
COP
4.67
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
10.70 kW
ηs
160 %
117 %
Prated
9.90 kW
10.70 kW
SCOP
4.08
3.00
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.73 kW
9.44 kW
COP Tj = -7°C
2.86
2.05
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.34 kW
6.11 kW
COP Tj = +2°C
3.92
2.82
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.99 kW
9.33 kW
COP Tj = +7°C
5.31
4.03
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
7.44 kW
6.77 kW
COP Tj = 12°C
7.15
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.73 kW
9.44 kW
COP Tj = Tbiv
2.86
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.46 kW
6.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.42
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.41 kW
3.86 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
20384 kWh
22040 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
124 %
COP
2.55
Heating up time
0:58 h:min
Standby power input
35.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
290 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.50 kW
13.43 kW
El input
3.42 kW
4.94 kW
COP
4.53
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
11.80 kW
ηs
155 %
119 %
Prated
10.00 kW
11.80 kW
SCOP
3.95
3.05
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.85 kW
10.45 kW
COP Tj = -7°C
2.54
2.05
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.60 kW
6.65 kW
COP Tj = +2°C
3.76
2.86
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.93 kW
9.42 kW
COP Tj = +7°C
5.40
4.13
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
14.93 kW
6.77 kW
COP Tj = 12°C
6.49
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.85 kW
10.45 kW
COP Tj = Tbiv
2.54
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.44 kW
7.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
7.15
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.56 kW
4.00 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
24394 kWh
24394 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.50 kW
13.43 kW
El input
3.42 kW
4.94 kW
COP
4.53
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
11.80 kW
ηs
155 %
119 %
Prated
10.00 kW
11.80 kW
SCOP
3.95
3.05
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.85 kW
10.45 kW
COP Tj = -7°C
2.54
2.05
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.60 kW
6.65 kW
COP Tj = +2°C
3.76
2.86
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.93 kW
9.42 kW
COP Tj = +7°C
5.40
4.13
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
14.93 kW
6.77 kW
COP Tj = 12°C
6.49
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.85 kW
10.45 kW
COP Tj = Tbiv
2.54
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.44 kW
7.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
7.15
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.56 kW
4.00 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
24394 kWh
24394 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.50 kW
13.43 kW
El input
3.42 kW
4.94 kW
COP
4.53
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
11.80 kW
ηs
155 %
119 %
Prated
10.00 kW
11.80 kW
SCOP
3.95
3.05
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.85 kW
10.45 kW
COP Tj = -7°C
2.54
2.05
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.60 kW
6.65 kW
COP Tj = +2°C
3.76
2.86
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.93 kW
9.42 kW
COP Tj = +7°C
5.40
4.13
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
14.93 kW
6.77 kW
COP Tj = 12°C
6.49
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.85 kW
10.45 kW
COP Tj = Tbiv
2.54
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.44 kW
7.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
7.15
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.56 kW
4.00 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
24394 kWh
24394 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.50 kW
13.43 kW
El input
3.42 kW
4.94 kW
COP
4.53
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
11.80 kW
ηs
155 %
119 %
Prated
10.00 kW
11.80 kW
SCOP
3.95
3.05
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.85 kW
10.45 kW
COP Tj = -7°C
2.54
2.05
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.60 kW
6.65 kW
COP Tj = +2°C
3.76
2.86
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.93 kW
9.42 kW
COP Tj = +7°C
5.40
4.13
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
14.93 kW
6.77 kW
COP Tj = 12°C
6.49
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.85 kW
10.45 kW
COP Tj = Tbiv
2.54
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.44 kW
7.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
7.15
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.56 kW
4.00 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
24394 kWh
24394 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.50 kW
13.43 kW
El input
3.42 kW
4.94 kW
COP
4.53
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
11.80 kW
ηs
155 %
119 %
Prated
10.00 kW
11.80 kW
SCOP
3.95
3.05
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.85 kW
10.45 kW
COP Tj = -7°C
2.54
2.05
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.60 kW
6.65 kW
COP Tj = +2°C
3.76
2.86
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.93 kW
9.42 kW
COP Tj = +7°C
5.40
4.13
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
14.93 kW
6.77 kW
COP Tj = 12°C
6.49
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.85 kW
10.45 kW
COP Tj = Tbiv
2.54
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.44 kW
7.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
7.15
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.56 kW
4.00 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
24394 kWh
24394 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
124 %
COP
2.55
Heating up time
0:58 h:min
Standby power input
35.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
290 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.50 kW
13.43 kW
El input
3.42 kW
4.94 kW
COP
4.53
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
11.80 kW
ηs
155 %
119 %
Prated
10.00 kW
11.80 kW
SCOP
3.95
3.05
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.85 kW
10.45 kW
COP Tj = -7°C
2.54
2.05
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.60 kW
6.65 kW
COP Tj = +2°C
3.76
2.86
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.93 kW
9.42 kW
COP Tj = +7°C
5.40
4.13
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
14.93 kW
6.77 kW
COP Tj = 12°C
6.49
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.85 kW
10.45 kW
COP Tj = Tbiv
2.54
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.44 kW
7.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
7.15
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.56 kW
4.00 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
24394 kWh
24394 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
124 %
COP
2.55
Heating up time
0:58 h:min
Standby power input
35.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
290 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.50 kW
13.43 kW
El input
3.42 kW
4.94 kW
COP
4.53
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
11.80 kW
ηs
155 %
119 %
Prated
10.00 kW
11.80 kW
SCOP
3.95
3.05
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.85 kW
10.45 kW
COP Tj = -7°C
2.54
2.05
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.60 kW
6.65 kW
COP Tj = +2°C
3.76
2.86
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.93 kW
9.42 kW
COP Tj = +7°C
5.40
4.13
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
14.93 kW
6.77 kW
COP Tj = 12°C
6.49
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.85 kW
10.45 kW
COP Tj = Tbiv
2.54
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.44 kW
7.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
7.15
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.56 kW
4.00 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
24394 kWh
24394 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
124 %
COP
2.55
Heating up time
0:58 h:min
Standby power input
35.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
290 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.50 kW
13.43 kW
El input
3.42 kW
4.94 kW
COP
4.53
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
11.80 kW
ηs
155 %
119 %
Prated
10.00 kW
11.80 kW
SCOP
3.95
3.05
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
8.85 kW
10.45 kW
COP Tj = -7°C
2.54
2.05
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
6.60 kW
6.65 kW
COP Tj = +2°C
3.76
2.86
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
5.93 kW
9.42 kW
COP Tj = +7°C
5.40
4.13
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
14.93 kW
6.77 kW
COP Tj = 12°C
6.49
5.44
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
8.85 kW
10.45 kW
COP Tj = Tbiv
2.54
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.44 kW
7.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
7.15
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.56 kW
4.00 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
24394 kWh
24394 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
124 %
COP
2.55
Heating up time
0:58 h:min
Standby power input
35.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
290 l