1,050 kg
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Heat output
2.80 kW
El input
0.66 kW
COP
4.25
Average Climate
EN 12102-1
Sound power level indoor
53 dB(A)
Sound power level outdoor
58 dB(A)
EN 14825
ηs
174 %
Prated
4.10 kW
SCOP
4.42
Tbiv
-7 °C
TOL
-10 °C
Pdh Tj = -7°C
3.70 kW
COP Tj = -7°C
2.60
Cdh Tj = -7 °C
Pdh Tj = +2°C
2.00 kW
COP Tj = +2°C
4.50
Cdh Tj = +2 °C
Pdh Tj = +7°C
1.50 kW
COP Tj = +7°C
5.70
Cdh Tj = +7 °C
Pdh Tj = 12°C
1.60 kW
COP Tj = 12°C
7.60
Cdh Tj = +12 °C
Pdh Tj = Tbiv
3.70 kW
COP Tj = Tbiv
2.60
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
WTOL
50 °C
Poff
5 W
PTO
20 W
PSB
5 W
PCK
0 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.60 kW
Annual energy consumption Qhe
1912 kWh