3,800 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
14.00 kW
El input
4.89 kW
5.04 kW
COP
3.27
2.78
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
63 dB(A)
63 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
126 %
117 %
Prated
13.00 kW
11.00 kW
SCOP
3.23
3.01
Tbiv
-10 °C
-10 °C
TOL
-15 °C
-15 °C
Pdh Tj = -7°C
11.90 kW
9.60 kW
COP Tj = -7°C
2.40
2.46
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
7.00 kW
5.90 kW
COP Tj = +2°C
3.30
3.47
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
4.70 kW
3.70 kW
COP Tj = +7°C
4.20
3.00
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
4.80 kW
4.50 kW
COP Tj = 12°C
3.80
3.60
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
13.50 kW
10.80 kW
COP Tj = Tbiv
2.10
2.00
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.50 kW
10.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.10
2.00
WTOL
65 °C
65 °C
Poff
60 W
60 W
PTO
60 W
60 W
PSB
60 W
60 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
Electricity
Supplementary Heater: PSUP
0.00 kW
0.20 kW
Annual energy consumption Qhe
8618 kWh
7424 kWh