2,800 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.30 kW
11.90 kW
El input
2.56 kW
4.28 kW
COP
4.81
2.78
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
dB(A)
dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
169 %
126 %
Prated
12.00 kW
13.00 kW
SCOP
4.29
3.23
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.52 kW
11.29 kW
COP Tj = -7°C
2.88
2.05
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
6.50 kW
7.31 kW
COP Tj = +2°C
4.15
3.14
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
4.12 kW
4.96 kW
COP Tj = +7°C
5.74
4.25
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
2.23 kW
2.37 kW
COP Tj = 12°C
5.40
4.94
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
10.52 kW
11.29 kW
COP Tj = Tbiv
2.88
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.01 kW
11.88 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
60 °C
60 °C
Poff
9 W
9 W
PTO
15 W
15 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.90 kW
Annual energy consumption Qhe
5726 kWh
8164 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.30 kW
16.10 kW
El input
3.66 kW
5.90 kW
COP
4.45
2.73
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
dB(A)
dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
169 %
128 %
Prated
16.00 kW
15.00 kW
SCOP
4.30
3.27
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
14.15 kW
12.90 kW
COP Tj = -7°C
2.72
2.04
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
8.92 kW
8.25 kW
COP Tj = +2°C
4.17
3.21
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
5.64 kW
5.45 kW
COP Tj = +7°C
5.86
4.32
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
2.47 kW
2.57 kW
COP Tj = 12°C
6.28
5.12
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
14.15 kW
12.90 kW
COP Tj = Tbiv
2.72
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.93 kW
11.16 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.41
1.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
60 °C
60 °C
Poff
9 W
9 W
PTO
41 W
41 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.10 kW
3.40 kW
Annual energy consumption Qhe
7687 kWh
9216 kWh