2,200 kg
Brine/Water Heat Pump
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
8.89 kW
8.54 kW
El input
1.83 kW
2.72 kW
COP
4.85
3.14
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
211 %
159 %
Prated
16.00 kW
16.00 kW
SCOP
5.48
4.18
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
9.80 kW
9.80 kW
COP Tj = -7°C
5.10
3.80
Pdh Tj = +2°C
6.00 kW
6.00 kW
COP Tj = +2°C
6.10
4.70
Pdh Tj = +7°C
5.70 kW
5.60 kW
COP Tj = +7°C
6.10
5.00
Pdh Tj = 12°C
5.70 kW
5.60 kW
COP Tj = 12°C
5.60
5.00
Pdh Tj = Tbiv
15.90 kW
16.00 kW
COP Tj = Tbiv
3.90
2.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.90 kW
16.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.90
2.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
65 °C
65 °C
Poff
2 W
2 W
PTO
30 W
30 W
PSB
7 W
7 W
PCK
30 W
30 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.10 kW
0.00 kW
Annual energy consumption Qhe
7218 kWh
9434 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
199 %
154 %
Prated
16.00 kW
16.00 kW
SCOP
5.18
4.05
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
14.20 kW
14.20 kW
COP Tj = -7°C
4.19
3.00
Pdh Tj = +2°C
8.70 kW
8.70 kW
COP Tj = +2°C
5.26
4.10
Pdh Tj = +7°C
5.70 kW
5.60 kW
COP Tj = +7°C
6.06
4.90
Pdh Tj = 12°C
5.80 kW
5.50 kW
COP Tj = 12°C
5.85
5.00
Pdh Tj = Tbiv
15.90 kW
16.00 kW
COP Tj = Tbiv
3.90
2.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.90 kW
16.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.90
2.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.98
0.99
WTOL
65 °C
65 °C
Poff
2 W
2 W
PTO
30 W
30 W
PSB
7 W
7 W
PCK
30 W
30 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.10 kW
0.00 kW
Annual energy consumption Qhe
6373 kWh
8167 kWh
Domestic Hot Water (DHW)
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
98 %
COP
2.45
Heating up time
01:04 h:min
Standby power input
50.0 W
Reference hot water temperature
50.0 °C
Mixed water at 40°C
240 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
98 %
COP
2.45
Heating up time
01:04 h:min
Standby power input
50.0 W
Reference hot water temperature
50.0 °C
Mixed water at 40°C
240 l
Water/Water Heat Pump
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
11.20 kW
10.90 kW
El input
1.84 kW
2.79 kW
COP
6.11
3.91
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
265 %
202 %
Prated
19.00 kW
19.00 kW
SCOP
6.82
5.25
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
11.60 kW
11.60 kW
COP Tj = -7°C
6.51
4.82
Pdh Tj = +2°C
7.30 kW
7.10 kW
COP Tj = +2°C
7.56
5.87
Pdh Tj = +7°C
7.30 kW
7.00 kW
COP Tj = +7°C
7.62
6.24
Pdh Tj = 12°C
7.30 kW
7.00 kW
COP Tj = 12°C
7.46
6.47
Pdh Tj = Tbiv
19.00 kW
19.00 kW
COP Tj = Tbiv
5.01
3.51
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
19.00 kW
19.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.01
3.51
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.96
0.98
WTOL
65 °C
65 °C
Poff
2 W
2 W
PTO
45 W
35 W
PSB
10 W
7 W
PCK
30 W
30 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6861 kWh
8907 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
265 %
202 %
Prated
19.00 kW
19.00 kW
SCOP
6.47
5.00
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
16.90 kW
16.90 kW
COP Tj = -7°C
5.34
3.82
Pdh Tj = +2°C
10.30 kW
10.30 kW
COP Tj = +2°C
6.61
5.08
Pdh Tj = +7°C
7.20 kW
7.00 kW
COP Tj = +7°C
7.50
5.93
Pdh Tj = 12°C
7.30 kW
7.10 kW
COP Tj = 12°C
7.61
6.28
Pdh Tj = Tbiv
19.00 kW
19.00 kW
COP Tj = Tbiv
5.01
3.51
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
19.00 kW
19.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.01
3.51
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.97
0.98
WTOL
65 °C
65 °C
Poff
2 W
2 W
PTO
45 W
35 W
PSB
10 W
7 W
PCK
30 W
30 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6070 kWh
7834 kWh
Domestic Hot Water (DHW)
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.82
Heating up time
00:58 h:min
Standby power input
45.0 W
Reference hot water temperature
45.0 °C
Mixed water at 40°C
235 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.82
Heating up time
00:58 h:min
Standby power input
45.0 W
Reference hot water temperature
45.0 °C
Mixed water at 40°C
235 l
Brine/Water Heat Pump
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
8.89 kW
8.54 kW
El input
1.83 kW
2.72 kW
COP
4.85
3.14
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
211 %
159 %
Prated
16.00 kW
16.00 kW
SCOP
5.48
4.18
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
9.80 kW
9.80 kW
COP Tj = -7°C
5.10
3.80
Pdh Tj = +2°C
6.00 kW
6.00 kW
COP Tj = +2°C
6.10
4.70
Pdh Tj = +7°C
5.70 kW
5.60 kW
COP Tj = +7°C
6.10
5.00
Pdh Tj = 12°C
5.70 kW
5.60 kW
COP Tj = 12°C
5.60
5.00
Pdh Tj = Tbiv
15.90 kW
16.00 kW
COP Tj = Tbiv
3.90
2.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.90 kW
16.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.90
2.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
65 °C
65 °C
Poff
2 W
2 W
PTO
30 W
30 W
PSB
7 W
7 W
PCK
30 W
30 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.10 kW
0.00 kW
Annual energy consumption Qhe
7218 kWh
9434 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
199 %
154 %
Prated
16.00 kW
16.00 kW
SCOP
5.18
4.05
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
14.20 kW
14.20 kW
COP Tj = -7°C
4.19
3.00
Pdh Tj = +2°C
8.70 kW
8.70 kW
COP Tj = +2°C
5.26
4.10
Pdh Tj = +7°C
5.70 kW
5.60 kW
COP Tj = +7°C
6.06
4.90
Pdh Tj = 12°C
5.80 kW
5.50 kW
COP Tj = 12°C
5.85
5.00
Pdh Tj = Tbiv
15.90 kW
16.00 kW
COP Tj = Tbiv
3.90
2.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.90 kW
16.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.90
2.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.98
0.99
WTOL
65 °C
65 °C
Poff
2 W
2 W
PTO
30 W
30 W
PSB
7 W
7 W
PCK
30 W
30 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.10 kW
0.00 kW
Annual energy consumption Qhe
6373 kWh
8167 kWh
Water/Water Heat Pump
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
11.20 kW
10.90 kW
El input
1.84 kW
2.79 kW
COP
6.11
3.91
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
265 %
202 %
Prated
19.00 kW
19.00 kW
SCOP
6.82
5.25
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
11.60 kW
11.60 kW
COP Tj = -7°C
6.51
4.82
Pdh Tj = +2°C
7.30 kW
7.10 kW
COP Tj = +2°C
7.56
5.87
Pdh Tj = +7°C
7.30 kW
7.00 kW
COP Tj = +7°C
7.62
6.24
Pdh Tj = 12°C
7.30 kW
7.00 kW
COP Tj = 12°C
7.46
6.47
Pdh Tj = Tbiv
19.00 kW
19.00 kW
COP Tj = Tbiv
5.01
3.51
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
19.00 kW
19.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.01
3.51
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.96
0.98
WTOL
65 °C
65 °C
Poff
2 W
2 W
PTO
45 W
35 W
PSB
10 W
7 W
PCK
30 W
30 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6861 kWh
8907 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
265 %
202 %
Prated
19.00 kW
19.00 kW
SCOP
6.47
5.00
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
16.90 kW
16.90 kW
COP Tj = -7°C
5.34
3.82
Pdh Tj = +2°C
10.30 kW
10.30 kW
COP Tj = +2°C
6.61
5.08
Pdh Tj = +7°C
7.20 kW
7.00 kW
COP Tj = +7°C
7.50
5.93
Pdh Tj = 12°C
7.30 kW
7.10 kW
COP Tj = 12°C
7.61
6.28
Pdh Tj = Tbiv
19.00 kW
19.00 kW
COP Tj = Tbiv
5.01
3.51
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
19.00 kW
19.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.01
3.51
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.97
0.98
WTOL
65 °C
65 °C
Poff
2 W
2 W
PTO
45 W
35 W
PSB
10 W
7 W
PCK
30 W
30 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6070 kWh
7834 kWh