Air Source Heat Pump 010
Heat Pump Type: Outdoor Air/Water
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
10.31 kW
9.28 kW
El input
2.31 kW
2.96 kW
COP
4.47
3.13
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
66 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
176 %
126 %
Prated
7.86 kW
7.26 kW
SCOP
4.47
3.24
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.95 kW
6.42 kW
COP Tj = -7°C
3.25
2.29
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.19 kW
4.11 kW
COP Tj = +2°C
4.47
3.20
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.02 kW
3.71 kW
COP Tj = +7°C
5.70
4.05
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.94 kW
4.12 kW
COP Tj = 12°C
8.34
5.69
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
6.95 kW
6.42 kW
COP Tj = Tbiv
3.25
2.29
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.41 kW
6.35 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
2.18
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
51 °C
51 °C
Poff
9 W
9 W
PTO
19 W
19 W
PSB
9 W
9 W
PCK
40 W
40 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.45 kW
0.91 kW
Annual energy consumption Qhe
3630 kWh
4634 kWh